Skip navigation

putin IS MURDERER

Please use this identifier to cite or link to this item: https://oldena.lpnu.ua/handle/ntb/34954
Full metadata record
DC FieldValueLanguage
dc.contributor.authorMusierowicz, K.-
dc.contributor.authorMarcinkowski, Z.-
dc.date.accessioned2017-01-12T09:51:27Z-
dc.date.available2017-01-12T09:51:27Z-
dc.date.issued2007-
dc.identifier.citationMusierowicz K. Fuzzy-logic algorithm for detection of intermittent earth faults / K. Musierowicz, Z. Marcinkowski // Вісник Національного університету «Львівська політехніка». – 2007. – № 596 : Електроенергетичні та електромеханічні системи. – С. 20–26. – Bibliography: 6 titles.uk_UA
dc.identifier.urihttps://ena.lpnu.ua/handle/ntb/34954-
dc.description.abstractIn the case of faults which are especially ‘difficult’ to detect, the effectiveness of the operation of protections can be improved using fuzzy logic. It refers mainly to the intermittent earth faults. The intermittent faults in the MV distribution grids are often unnoticed by the conventional earth fault protections and, consequently, are not eliminated. In such faults, the periodically non-stationary measuring signals are generated. By smoothing the waveform, for example by averaging it within an appropriate interval, the criterion value falls below the start-up value and the fault discrimination using traditional binary logic (true/false – fault/ lack of fault) is not ensured. The fuzzy logic fits here better. In the work, the protection with fuzzy decision system is proposed.uk_UA
dc.language.isoenuk_UA
dc.publisherВидавництво Національного університету «Львівська політехніка»uk_UA
dc.titleFuzzy-logic algorithm for detection of intermittent earth faultsuk_UA
dc.typeArticleuk_UA
Appears in Collections:Електроенергетичні та електромеханічні системи. – 2007. – №596

Files in This Item:
File Description SizeFormat 
5_20-26.pdf144.54 kBAdobe PDFView/Open
Show simple item record


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.